| 2004-03-04 00:00:00 | DENIED: | | | PLANS INDICATE DUCTS PENETRATING RATED | | | WALLS.FIRE DAMPERS ARE NOT INDICATED | | | ON THE PLAN.PER 2001 FBC(M) 607.6, | | | SPECIFIC LOCATION OF FIRE DAMPERS AND | | | ACCESS DOOR ARE TO BE INDENTIFIED ON | | | THE PLAN. | | | | | | EXEMPTIONS FOR FIRE DAMPERS SHALL COMPLY | | | WITH 2001 FBC(M) 607.1.3 #3 ITEMS 1 THR | | | OUGH 4.PLEASE CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|