| 2003-06-13 00:00:00 | 1) DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION TO COMPLY WITH NFPA 241. |
| | |
| | 2) IT APPEARS DOORS 103, AND 106 ARE |
| | LOCATED IN RATED FIRE WALLS. DOORS |
| | ACCORDING TO SCHEDULE ARE NOT RATED. |
| | |
| | 3) DOORS 101, 107, 107B, 114, 114B IF |
| | SUBJECT TO A 100 OR MORE PERSONS SHALL |
| | BE EQUIPPED WITH PANIC HARDWARE. |
| | |
| | 4) IT DOES NOT APPEAR THAT DOOR 201 |
| | NEEDS PANIC HARDWARE. |
| | |
| | 5) DOES THE EXISTING STAIR OPPOSITE OF |
| | DOOR 114B HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 6) ARE THE NEW STORAGE ROOM WALLS |
| | 108 AND 113 RATED OR NON RATED. |
| | |
| | 7) HOW IS PLATFORM 099 HANDICAP |
| | ACCESSIBLE. |
| | |
| | 8) PROVIDE DETAILS ON RISE, RUN, AND |
| | TREAD DEPTH AND STAIR WIDTH FOR STAIR |
| | # 104. |
| | |
| | 9) ENSURE BUILDING ADDRESS. MINIMUM 6" |
| | HIGH ON PROPER ELEVATION. |
| | |
| | 10) ARE EMERGENCY LIGHTS PRESENT IN |
| | MAIN SEATING AREA. |
| | |
| | 11) PLEASE INDICATE LOCATIONS OF |
| | HANDICAPPED SEATING IN CHAPEL 100. |
| | |
| | 12) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS. |
| | |
| | 13) DOOR 104 DOES NOT NEED PANIC |
| | HARDWARE. |
| | |
| | 14) ALL NEW STAIRS AND RAMPS SHALL HAVE |
| | HANDRAILS ON BOTH SIDES. |
| | |
| | 15) PLEASE INDICATE EXISTING FIRE |
| | SPRINKLER OR FIRE ALARM SYSTEM |
| | EQUIPMENT CONTAINED WITHIN THE |
| | BUILDING. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |