| Plan Review Notes For Permit 03052306 |
| Permit Number |
03052306 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-05 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES AND | | | ADD THE FOLLOWING TO THE PLANS FOR CODE | | | COMPLIANCE. | | | | | | 1} THE RISER DIAGRAM AND LOAD | | | CALCULATION ATTACHED TO THE PLAN IS NOT | | | IN THE SCOPE OF WORK DESCRIBED ON THE | | | PERMIT APPLICATION OR PART OF THE | | | SIGNED AND SEALED PLANS.ALSO THE | | | RELOCATED METER IS NOT IN THE | | | SCOPE.PLEASE HAVE THE ARCHITECT OF | | | RECORD ADD THIS TO THE PLANS AND | | | INCLUDE IN THE PROJECT VALUATION,OR | | | APPLY FOR A SEPARATE PERMIT FOR THAT | | | WORK. | | | | | | 2} PLEASE SUPPLY A PANEL SCHEDULE. | | | | | | 3} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 4} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 5} SMOKE DETECTORS ARE REQUIRED INSIDE | | | AND OUTSIDE BEDROOMS PER 8-1.4.2 | | | NFPA-72. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|