| 2003-06-11 00:00:00 | ******CORRECTIONS******* |
| | |
| | 1.)ADDITIONAL PERMITS REQUIRED. |
| | |
| | 2.)WINDOW B IS REQUIRED TO BE SAFETY |
| | GLASS, FBC2405.2.1. |
| | |
| | 3.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN.IF THE ADDITION AREA IS GREATER |
| | THAN 25% OF THE EXISTING, COMPLY WITH |
| | FBC 3401.7.1.SHOW EMERGENCY EGRESS |
| | FOR BEDROOMS, SMOKE DETECTORS FOR |
| | EXISTING BEDROOMS, POOL SAFETY |
| | COMPLIANCE, AND SAFETY GLASS COMPLIANCE. |
| | |
| | 4.ENERGY CALCS REQUIRED FBC13-101.2. |
| | |
| | 5.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION.233-5025 |
| | |
| | 6.)PROVIDE CALCULATIONS FOR THE |
| | REAR ELEVATION TO SHOW COMPLIANCE WITH |
| | TABLE 600 (20% MAX OF OPENINGS, TYPE |
| | VI CONSTRUCTION UNPROTECTED). |
| | |
| | 7.)THE ADDITION MUST COMPLY WITH |
| | THE RESIDENTIAL SWIMMING POOL SAFETY |
| | ACT 515 FS. |
| | |
| | 8.)SOFFIT VENTS ARE TO COMPLY WITH |
| | FBC 2309.7, CANNOT "MATCH EXISTING". |
| | SPECIFY SIZE AND SPACING OR NUMBER. |
| | |
| | 9.)ATTIC ACCESS REQUIED, FBC2309.6. |
| | |
| | 10.)SPECIFY CEILING INSULATION ON THE |
| | WALL SECTION (A5).BEFORE RESUBMITTING, |
| | BE SURE THAT THE INSULATION ON THE PLAN |
| | IS CONSISTENT WITH THE MINIMUMS ON THE |
| | ENERGY CALCS. |
| | |
| | 11.)FIRESTOP REQUIRED, FBC 705.5 |
| | (REVISE WALL SECTION A5). |
| | |
| | 12.)ADDITIONAL FEES REQUIRED. |