| Date |
Text |
| 2003-07-08 00:00:00 | ******CORRECTIONS******** |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)THE ORIGINAL RECEIPT SHOWING THAT |
| | IMPACT FEES HAVE BEEN PAID MUST BE |
| | ATTACHED TO THE APPLICATION. |
| | |
| | 3.)THE AREA CALCULATIONS SHOULD SHOW |
| | SUBTOTALS FOR CONDITIONED AND UNCONDIT. |
| | SPACE.IMPACT FEES WERE PAID ON A |
| | SQUARE FOOTAGE LESS THAN THE TOTAL A/C |
| | SQUARE FOOTAGE.CALL 233-5025 TO |
| | DETERMINE WHETHER OR NOT IMPACT FEES |
| | NEED TO BE ADJUSTED. |
| | |
| | 4.)THE TOTAL CONDITIONED FLOOR AREA |
| | ON THE ENERGY CALC IS INCORRECT. |
| | |
| | 5.)ADDITIONAL FEES ARE DUE (VALUE |
| | ADJUSTMENT); $755.07. |
| | |
| | 6.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 7.)THE 2ND FLOOR BATHROOM WINDOW MUST |
| | COMPLY WITH FBC 2405.1 (SAFETY GLASS). |
| | |
| | 8.)PROVIDE DETAILS FOR THE GUARDRAIL |
| | AND THE STAIR RAIL, GIVING ALL |
| | DIMENSIONS AND SHOWING COMPLIANCE WITH |
| | FBC 1608.2. |
| | |
| | 9.)PROVIDE A ROOF SHEATHING ATTACHMENT |
| | SCHEDULE. |
| | |
| | 10.) SHOW THE FIRESTOP FOR THE FRAME |
| | WALL, FBC 705.3. |
| | |
| | 11.)THE ENERGY CALC DOES NOT SHOW THE |
| | 2X6 EXTERIOR FRAME WALL.PROVIDE A |
| | WALL LEGEND. |
| | |
| | 12.)FOR CLARIFICATION, EXPLAIN THE |
| | DIFFERENCE BETWEEN COLUMN A AND COLUMN |
| | B.THE TEXT DESCRIPTIONS ARE THE SAME. |
| | (SHEET 6). |
| | |
| | 13.)THE 2ND FLOOR PLAN (SHEET 4) SHOWS |
| | FRENCH DOORS AT THE OPEN AREA.SHEET |
| | 7 SHOWS S/H WINDOWS AT THAT LOCATION. |
| | |
| | 14.)SHOW INSULATION FOR THE ADJACENT |
| | WALL, SHEET 6. |
| | |
| | 15.)THE SQUARE FOOTAGE FOR 10A ON THE |
| | ENERGY CALC IS INCORRECT. |
| | |
| | 16.)THE FOLLOWING PRODUCT APPROVALS |
| | ARE NOT LEGIBLE: |
| | PREMDOOR |
| | GARAGE DOOR |
| | SHUTTERS |
| | PROVIDE TWO LEGIBLE COPIES.SEE |
| | ATTACHED FOR INSTRUCTIONS TO OBTAIN |
| | PRODUCT APPROVALS ONLINE. |
| | |
| | 17.)THE FOLLOWING PRODUCT APPROVALS |
| | ARE REQUIRED BUT WERE NOT SUBMITTED: |
| | DOUBLE FRENCH DOOR (UNLESS PREMDOOR |
| | IS USED IN ALL OF THE LOCATIONS) |
| | SINGLE FRENCH DOOR |
| | GLASS BLOCK |
| | MULLIONS |
| | EXTERIOR SIDE DOOR |
| | |
| | 18.)THE REPORT FOR THE FIXED GLASS |
| | WINDOWS USED ASTM E330-90 AS THE |
| | STRUCTURAL TEST.FBC35 SPECIFIES |
| | ASTM E330-84.SUBMIT TWO COPIES OF |
| | PRODUCT APPROVALS FOR THE FIXED GLASS |
| | WINDOW. |
| | |
| | WHEN RESUBMITTING, REPLACE ANY SHEETS |
| | WHICH HAVE CHANGED WITH NEW SHEETS. |
| | SUBMIT THE OLD SHEETS SEPARATELY, |
| | MARKED.SUBMIT THIS CORRECTION LIST |
| | WITH A WRITTEN EXPLANATION AS TO HOW |
| | EACH ITEM WAS ADDRESSED.ALL CHANGES |
| | SHOULD BE CLEARLY MARKED WITH EITHER |
| | CLOUDS OR TRIANGLES. |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |