| 2003-07-18 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) THE SITE SPECIFIC ENGINEERING DOES |
| | NOT CORRESPOND TO THE WINDOW SIZES ON |
| | THE PLANS. THE JOB/SITE LOCATION IS NOT |
| | LISTED ON THE FORM. THE DESIGNER OF |
| | RECORD IS REQUIRED TO SIGN AND SEAL THE |
| | FORM OR PROVIDE A SIGNED AND SEALED |
| | LETTER REFERENCING THE PRODUCTS AND |
| | JOB LOCATION. |
| | |
| | 2) SUBMIT A LETTER FROM AL-FAROOQ CORP. |
| | (SIGNED AND SEALED) STATING THAT THE |
| | SITE SPECIFIC DRAWINGS FOR THE MULLIONS |
| | HAVE BEEN REVIEWED AND APPROVED BY THEM |
| | AS REQUIRED BY THE PRODUCT EVALUATION |
| | DOCUMENT THAT WAS SUBMITTED. SEE NOTES |
| | #3 AND D ON DRAWING NO. M96-08B. SHEET 1 |
| | OF 3. |
| | |
| | 3)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - GLASS BLOCK |
| | - 16' WIDE GARAGE DOOR |
| | - DOUBLE OUTSWING FRONT DOORS |
| | - STORM PANELS |
| | |
| | 4)THE PRELIMINARY SOIL REPORT RECOMMENDS |
| | ADDITIONAL TESTING. CONTRACTOR WILL BE |
| | CONTINUING AT HIS OWN RISK WITHOUT |
| | ADDITIONAL TESTING. |
| | |
| | 5) STRUCTURE IS LOCATED IN AN "A0" FLOOD |
| | ZONE AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | 6) THE ROOF SLOPE ON THE KNEZEVICH |
| | SCHEDULE FOR THE STORM PANELS HAS THE |
| | WRONG ROOF PITCH LISTED. THE PLANS |
| | SPECIFY A 5 INCH PER FOOT ROOF SLOPE. |
| | THE NEGATIVE PRESSURE FOR OPENING #14 |
| | IS HIGHER ON THE KNEZEVICH SCHEDULE THAN |
| | LISTED ON THE INSTALLATION SCHEDULE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |