| 2003-07-18 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) DETAIL 11 ON A5 SPECIFIES A HANGER |
| | FASTENED TO A MASONRY WALL WITH (2) 5/8" |
| | THROUGH BOLTS ON EACH SIDE. PLEASE |
| | CORRECT. |
| | |
| | 2) THE PRODUCT APPROVAL FOR THE GARAGE |
| | DOOR IS MISSING PAGES AND THE DRAWING IS |
| | NOT LEGIBLE. |
| | |
| | 3) THE PRODUCT APPROVAL FOR THE DOUBLE |
| | OUTSWING DOOR IS ILLEGIBLE. |
| | |
| | 4) THE PRODUCT APPROVAL FOR THE SLIDING |
| | GLASS DOOR IS MISSING PAGS 4-6 OF THE |
| | APPROVED DRAWINGS. |
| | |
| | 5)THE PRELIMINARY SOIL REPORT RECOMMENDS |
| | ADDITIONAL TESTING. CONTRACTOR WILL BE |
| | CONTINUING AT HIS OWN RISK WITHOUT |
| | ADDITIONAL TESTING. |
| | |
| | 6) THE SITE SPECIFIC ENGINEERING DOES |
| | NOT LIST WINDOW #11 FROM THE PLANS. THIS |
| | IS THE 96"X 72" F.G. WINDOW WITH THE |
| | 96"X 23" F.G. ABOVE IT. THE NEGATIVE |
| | WINDLOAD PRESSURE LISTED ON THE PLANS |
| | FOR WINDOWS #14 AN #15 (-45.3PSF) |
| | EXCEEDS THE DESIGN PRESSURE SPECIFIED ON |
| | THE SITE SPECIFIC PRODUCT APPROVAL. |
| | |
| | 7) SUBMIT A SIGNED AND SEALED LETTER |
| | FROM AL-FAROOQ CORPORATION STATING THAT |
| | THE SITE SPECIFIC DRAWINGS FOR THE |
| | MULLIONS HAVE BEEN REVIEWED AND APPROVED |
| | BY THEM AS REQUIRED BY THE PRODUCT |
| | EVALUATION DOCUMENT THAT WAS SUBMITTED. |
| | SEE NOTES #3 AND D ON DRAWING NUMBER |
| | M96-08B SHEET 1 OF 3. |
| | |
| | 8) THE SLOPE ON THE KNEZEVICH WINDLOAD |
| | SCHEDULE IS INCORRECT. THE PLANS |
| | INDICATE A 5/12 PITCH. THE STORM PANEL |
| | INSTALLATION SCHEDULE LISTS A PRESSURE |
| | OF -74.9 PSF FOR OPENINGS 5,6 AND 14, |
| | WITH PANEL LENGTHS OF 108". THE MAXIMUM |
| | PRESSURE LISTED ON THE PRODUCT APPROVAL |
| | IS -74.3PSF FOR PANELS UP TO 70" IN |
| | LENGTH AND -72 FOR ALL OTHERS. SEE PAGES |
| | 13, 14 AND 15 OF THE PRODUCT APPROVAL. |
| | SUBMIT CORRECT INSTALLATION SCHEDULE OR |
| | APPLY UNDER A SEPARATE PERMIT. |
| | |
| | 9) STRUCTURE IS LOCATED IN A "AO" FLOOD |
| | ZONE AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |