| 2003-08-18 00:00:00 | ******CORRECTIONS****** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)ADDITIONAL FEES DUE; $705.57. |
| | |
| | 3.)PROVIDE THE RECEIPT FOR THE IMPACT |
| | FEES. |
| | |
| | 4.)SEE PREVIOUS LIST #11; THE CATALOG |
| | REQUIRES 20 NAILS; PLAN STILL SHOWS 16 |
| | (A6 AND A7). |
| | |
| | 5.)SEE PREVIOUS LIST #13; REFER TO |
| | FBC705.3 AND FBC2305.2.2.THE |
| | DRAFTSTOPPING SHOWN DOES NOT DIVIDE THE |
| | FLOOR/CEILING ASSEMBLY INTO AREAS LESS |
| | THAN 500 SF. |
| | |
| | 6.)ROOF ON THE TYPICAL WALL SECTION |
| | (A8) NOW SHOWS TILE ON 15# PAPER.IS |
| | THIS CORRECT? |
| | |
| | 7.)REFER TO PREVIOUS LIST, #16.THE |
| | BUCK ATTACHMENTS ARE STILL NOT ON THE |
| | PLAN.PLEASE PROVIDE. |
| | |
| | 8.)TYPICAL WALL SECTION SHOWS SPRAY |
| | FOAM INSULATION ON THE TOP CHORD OF THE |
| | TRUSS; INSULATION WHICH WAS PREVIOUSLY |
| | SHOWN ON THE BOTTOM CHORD IS NO LONGER |
| | ON THE DETAIL.FBC13-604.1.ABC.1, |
| | PRESCRIPTIVE REQUIREMENTS FOR METHOD A, |
| | REQUIRES R19 INSULATION ON THE CEILING. |
| | |
| | 9.)PROVIDE FIREBLOCK AT STAIRS, |
| | FBC2305.1.4(3). |
| | |
| | 10.) PROVIDE THE TEST REPORT FOR THE |
| | METAL GLAZED DOORS.ADDITIONAL |
| | INFORMATION IS REFERRED TO ON THE |
| | REPORT AS BEING AVAILABLE ON THEIR |
| | WEBSITE. |
| | |
| | 11.) THE PLAN SHOWS A 24 EGRESS WINDOW. |
| | IF YOU ARE INSTALLING A 25 SINGLE HUNG, |
| | CHANGE THE PLAN TO REFLECT THIS TO |
| | COMPLY WITH FBC1005.4. |
| | |
| | 12.) SEE PREVIOUS LIST #19.I AM STILL |
| | UNCLEAR AS TO WHERE THE IMPACT CASEMENT |
| | WINDOW IS TO BE INSTALLED.THE WINDOW |
| | CHANGES MADE WERE FOR FIXED WINDOWS. |
| | PRODUCT APPROVAL IS FOR CASEMENT IMPACT. |
| | THERE AREN'T ANY CASEMENT WINDOWS SHOWN |
| | ON THE PLAN. |