| Plan Review Notes For Permit 03052140 |
| Permit Number |
03052140 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-28 00:00:00 | FAIL | | | --------------------------------------- | | | 1. DUCT SIZES AND CFMS NOT SHOWN ON | | | PLAN | | | 2. DRYER EXHAUST REQUIRED PER FBC(M) | | | SECTION 504.1 | | | 3. EF 2,3,4 NOT SHOWN ON FAN SCHEDULE | | | 4. NO A/C DROPS SHOWN IN DEN/STUDY | | | 5. PROTECTION FROM VEHICLE DAMAGE | | | REQUIRED FOR AHU-2 PER 303.4 | | | 6. SHOW COMPLIANCE WITH EITHER SEC 402 | | | OR 403.3 (FRESH AIR REQUIREMENTS) | | | | | | REVIEWED BY: RONALD J REGUEIRO | | | ANY QUESTIONS PLEASE CALL 561-805-6734 |
|