2003-06-28 00:00:00FAIL
 ---------------------------------------
 1. DUCT SIZES AND CFMS NOT SHOWN ON
 PLAN
 2. DRYER EXHAUST REQUIRED PER FBC(M)
 SECTION 504.1
 3. EF 2,3,4 NOT SHOWN ON FAN SCHEDULE
 4. NO A/C DROPS SHOWN IN DEN/STUDY
 5. PROTECTION FROM VEHICLE DAMAGE
 REQUIRED FOR AHU-2 PER 303.4
 6. SHOW COMPLIANCE WITH EITHER SEC 402
 OR 403.3 (FRESH AIR REQUIREMENTS)
  
 REVIEWED BY: RONALD J REGUEIRO
 ANY QUESTIONS PLEASE CALL 561-805-6734