2003-06-27 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLAN AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE SERVICE IS DESIGNED @ 400 AMPS.
 THE GROUNDING ELECTRODE CONDUCTOR SHOULD
 BE 1/0 PER 250-66.
  
 3} THE AMPERE RATINGS FOR THE A/C SYSTEM
 ARE DIFFERENT IN THE LOAD CALCS,THE
 PANEL SCHEDULE,AND ON THE MECHANICAL
 SHEET.PLEASE CORRELATE,ADJUST
 CALCULATION TO REFLECT ACTUAL
 CONDITIONS.
  
 4} THE LOAD CALCULATIONS INDICATE A 200
 AMP SERVICE,THERE ARE 2-200 AMP MAINS ON
 THE PLANS,PLEASE CLARIFY.
  
 5} THE WATER HEATER IS SHOWN AS 6 KW IN
 THE CALCS AND SHOWN ON A 30 AMP BREAKER
 ON THE SCHEDULE,PLEASE CORRELATE.
  
 6} THE PHASE "C" MARKING ON THE SCHEDULE
 SHOULD BE CHANGED TO PHASE "B".
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 8} ADD A RECEPTACLE IN THE "NOOK"
 TO COMPLY WITH 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW