Date Text
2003-07-07 00:00:00*******CORRECTIONS*******
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 4.)THE NUMBERS ON THE N & S PROPERTY
 LINES OF THE SITE PLAN (S1) DO NOT MATCH
 THE SURVEY.
  
 5.)ADDITIONAL FEES DUE; $705.57.
  
 6.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE ORIGINAL RECEIPT ATTACHED TO THE
 APPLICATION.THIS MAY BE DONE BEFORE
 RESUBMITTAL OR AFTER THE PLANS ARE
 APPROVED BUT BEFORE A PERMIT CAN BE
 ISSUED.233-5025
  
 7.)FOUNDATION NOTES, 3A, "THREE FEET"
 SHOULD BE "FIVE FEET" AS PER SOILS
 REPORT.
  
 8.)GENERAL NOTES #22, A2, SPECS R5
 INSULATION FOR THE BLOCK WALLS.THE
 WALL SECTION SHOWS 3.8 (A8).THE ENERGY
 CALC REQUIRES A MINIMUM OF 4.2.
  
 9.)THE SINGLE HUNG WINDOW AT THE TUB
 (A5) MUST COMPLY WITH FBC2405.1 (SAFETY
 GLASS REQUIREMENT).
  
 10.) THE GIRDER CONNECTION, ROOF FRAMING
 NOTES, SPECIFIES A SEMCO ATTACHMENT.
 THEY ARE NO LONGER IN BUSINESS.
  
 11.) THE TYPICAL STRAPS AND BLOCKING
 DETAIL (A6 AND A7) SPECIFIES SIMPSON
 HETAL 20 WITH 16-10D NAILS, MAX UPLIFT
 OF 1890.THE 2003 CATALOG REQUIRES
 20-10DX1 1/2 IN ORDER TO OBTAIN THE
 1890 MAX UPLIFT.
  
 12.)TYPICAL WALL SECTION, SHOW THE
 1 1/2" WATERSTOP, 4" ABOVE GRADE, 12"
 BELOW GRADE (SHOWN ON THE FOOTER DETAIL
 BUT NOT ON THE WALL SECTION).
  
 13.)DRAFTSTOP REQUIRED, FBC 705.3.
  
 14.)THE TYPICAL WALL SECTION SHOWS
 FIBERGLASS SHINGLES; ELEVATION AND
 PRODUCT APPROVALS ARE FOR CEMENT TILE.
  
 15.)USE OF THE BEVELED BUCK (A8) IS IN
 CONFLICT WITH THE PRODUCT APPROVALS.
  
 16.)THE DOOR BUCK DETAIL AND WINDOW
 BUCK DETAIL REFER TO ATTACHMENTS NOT
 ON THE PLAN.
  
 17.)THE STAIR AND GUARD RAILS ARE TO
 COMPLY WITH FBC1608.2.
  
 18.)GIVE STAIR DIMENSIONS TO COMPLY
 WITH FBC1005.3.
  
 19.)PRODUCT APPROVALS FOR AN IMPACT
 CASEMENT WINDOW WERE SUBMITTED.ALL OF
 THE WINDOWS ON THE PLAN ARE SINGLE
 HUNG OR FIXED.PLEASE CLARIFY.
  
 20.)THE WIND EXPOSURE A2 SHOULD BE
 A,B,C OR D; FBC1606.1.8.
  
 21.)PROVIDE TWO COPIES OF PRODUCT
 APPROVALS:
 MULLIONS (PAS SUBMITTED ARE EXPIRED)
 FRENCH DOOR
 SIDELITES
 ENTRY DOOR
 24 EGRESS WINDOW
 GLASS BLOCK
  
 22.)THERE IS A DETAIL ON THE PLAN,
 BUTT GLASS FRAMING.NUMBER THIS DETAIL
 AND GIVE A CORRESPONDING MARK ON THE
 FLOOR PLAN WHERE THIS IS TO BE
 INSTALLED.GIVE A DETAILED SHOP
 DRAWING AND RATIONAL ANALYSIS OR TEST
 DATA ON THE PLAN FBC2406.2.
  
 23.) A8, FIRE RATED ATTIC ACCESS, REFERS
 TO SFBC, A BUILDING CODE NO LONGER USED.
 THE MINIMUM SIZE FOR THE ATTIC ACCESS
 IS 20X36 FBC2309.6.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER