| Plan Review Notes For Permit 03052075 |
| Permit Number |
03052075 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-02 00:00:00 | PROVISO: | | | | | | 1.PLAN SHEET 2, SECTION VIEW OF HOOD, | | | FANS, AND DUCTWORK.ROOF TERMINATION | | | INDICATES THE FAN TERMINATING CLOSE TO | | | THE PARAPET/ROOF.PLEASE CLARIFY THE | | | DISTANCE BETWEEN THE FAN & PARAPET AS | | | WELL AS THE MATERIAL. | | | | | | PLEASE NOTE AS PER 2001 FBC(M) | | | 506.3.14.2, EXHAUST OUTLETS SHALL BE | | | LOCATED NOT LESS THAN 10' HORIZONTALLY | | | FROM PARTS OF THE SAME OR CONTIGUOUS | | | BUILDINGS. | | | | | | 2.ADDITIONAL PERMIT REQUIRED FOR FIRE | | | SUPRESSION.PLEASE PROVIDE PLANS WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|