| Plan Review Notes For Permit 03051981 |
| Permit Number |
03051981 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-29 00:00:00 | | | | DENIED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION WITH REGARD TO THE | | | RELOCATION OF THE FLOOR BOXES. | | | | | | 1} A LETTER FROM THE MANAGEMENT OF ONE | | | WATERMARK STATING THEIR APPROVAL FOR | | | DECK CUTTING IN THE UNITS. | | | | | | 2} A LETTER FROM THE STRUCTURAL ENGINEER | | | OF RECORD VERIFYING HIS APPROVAL OF THE | | | OF THE DEPTHS AND LOCATION OF ANY CUTS | | | BEING MADE AND THE FLOOR BOX SYSTEM | | | BEING USED. | | | | | | 3} PLEASE PROVIDE X-RAYS OF THE AREA TO | | | BE CUT INDICATING ANY SUCH CUTS WILL NOT | | | COMPROMISE THE INTEGRITY OF THE | | | STRUCTURAL SYSTEM. | | | | | | PLEASE HAVE ALL DOCUMENTS BEING | | | SUBMITTED SIGNED AND SEALED BY THE | | | ENGINEER OF RECORD. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|