Plan Review Notes
Plan Review Notes For Permit 03051981
Permit Number 03051981
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-29 00:00:00PLEASE PROVIDE AN ANALYSIS OF THE
 EFFECTS OF THE ADDED FLOOR LOADS FROM
 THE STONE FLOORING TO BE INSTALLED,
 PREPARED BY AN ENGINEER OR ARCHITECT.
 SEE FBC 104.2.
  
 PROVIDE SPECIFIC CONSTRUCTION METHODS
 AND DETAIL FOR THE CUTTING OF THE POST
 TENSION FLOORS.
  
 PLEASE NOTE THE METHOD OF THE
 INSTALLATION OF THE WOOD FLOOR.