Plan Review Notes
Plan Review Notes For Permit 03051969
Permit Number 03051969
Review Stop P
Sequence Number 2
Notes
Date Text
2003-07-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: (COMMENT #5)
 SINKS SHALL COMPLY WITH 11-4.24 AND ALL
 SUBSECTIONS. SHOW KNEE CLEARANCE SECTION
 11-4.24.3, CLEAR FLOOR SPACE 11-4.24.5,
 EXPOSED PIPES AND SURFACES 11-4.24.6, &
 FAUCETS 11-4.24.7. MECHANIC'S BREAK ROOM
 SHALL COMPLY ALSO.
 2) INFORMATIONAL ALL DRINKING FOUNTAINS
 SHALL COMPLY PER SECTION 11-4.1.3(10)(B)
 AS THERE ARE ONLY ONE ON EACH FLOOR AS
 INDICATED BY RESPONSE TO COMMENT #2 OF
 PREVIOUS REVIEW.
 3) FROM PREVIOUS REVIEW: (COMMENT #11)
 MANUFACTURE INFORMATION REQUIRED FOR
 SUMP PUMP. SUBMIT MANUFACTURE CUT SHEETS
 FOR THIS PUMP. 104.2.1 & PLMB. SECTION
 303.4
 4) THE VENT INSTALLED FOR THE EWC IN THE
 REPAIR AREA IS NOT INSTALLED PROPERLY.
 THE TRAP IS AN "S" TRAP AND THE VENT
 SHALL BE SHOWN AS A STACK VENT FOR THE
 EWC.
 5) TABLE 906.1 THE TRAP FOR THE TRENCH
 DRAIN IN THE REPAIR AREA IS OVER THE
 MAXIMUM ALLOWABLE DISTANCE FROM THE VENT
 PLACE VENT IN WALL AS CLOSE AS POSSIBLE
 AND PUT TRAP 12' FROM VENT. AT TOP OF
 THE TRAP PUT IN A CLEANOUT AND TEE OFF
 TRAP RISER TO TRENCH DRAIN. SEE ATTACHED
 SHEET FOR EXAMPLE.
 6) THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2
  
 REVIEW BY KEN STEVENS