| 2003-07-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) FROM PREVIOUS REVIEW: (COMMENT #5) |
| | SINKS SHALL COMPLY WITH 11-4.24 AND ALL |
| | SUBSECTIONS. SHOW KNEE CLEARANCE SECTION |
| | 11-4.24.3, CLEAR FLOOR SPACE 11-4.24.5, |
| | EXPOSED PIPES AND SURFACES 11-4.24.6, & |
| | FAUCETS 11-4.24.7. MECHANIC'S BREAK ROOM |
| | SHALL COMPLY ALSO. |
| | 2) INFORMATIONAL ALL DRINKING FOUNTAINS |
| | SHALL COMPLY PER SECTION 11-4.1.3(10)(B) |
| | AS THERE ARE ONLY ONE ON EACH FLOOR AS |
| | INDICATED BY RESPONSE TO COMMENT #2 OF |
| | PREVIOUS REVIEW. |
| | 3) FROM PREVIOUS REVIEW: (COMMENT #11) |
| | MANUFACTURE INFORMATION REQUIRED FOR |
| | SUMP PUMP. SUBMIT MANUFACTURE CUT SHEETS |
| | FOR THIS PUMP. 104.2.1 & PLMB. SECTION |
| | 303.4 |
| | 4) THE VENT INSTALLED FOR THE EWC IN THE |
| | REPAIR AREA IS NOT INSTALLED PROPERLY. |
| | THE TRAP IS AN "S" TRAP AND THE VENT |
| | SHALL BE SHOWN AS A STACK VENT FOR THE |
| | EWC. |
| | 5) TABLE 906.1 THE TRAP FOR THE TRENCH |
| | DRAIN IN THE REPAIR AREA IS OVER THE |
| | MAXIMUM ALLOWABLE DISTANCE FROM THE VENT |
| | PLACE VENT IN WALL AS CLOSE AS POSSIBLE |
| | AND PUT TRAP 12' FROM VENT. AT TOP OF |
| | THE TRAP PUT IN A CLEANOUT AND TEE OFF |
| | TRAP RISER TO TRENCH DRAIN. SEE ATTACHED |
| | SHEET FOR EXAMPLE. |
| | 6) THERMAL EXPANSION CONTROL IS REQUIRED |
| | PER SECTION 607.3.2 |
| | |
| | REVIEW BY KEN STEVENS |