2003-07-26 00:00:00PER CONVERSATION WITH MR. DON BOITNOTT
 ON 7-28-03.
 CORRIDOR 121 (FIRE EGRESS HALL) -
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 1) A DETAIL OF THE WALL AND CEILING
 ASSEMBLY.INDICATE WHERE THE WALL
 RATING ENDS.
  
 2) AS PER OUR CONVERSATION THIS IS A
 DUCTED SYSTEM (NO PLENUM), PROVIDE DUCT
 SIZE BETWEEN THE TRANSFER GRILLES.
  
 3) CEILING FIRE DAMPERS REQUIRED AS PER
 2001 FBC(M) 607.2.PER OUR CONVERSATION
 SECTION 705.1.2.2.1, EXCEPTIONS #2,
 EXCEPTIONS EXPLAINED IN THIS SECTION ARE
 FOR WALLS OR PARTITIONS.CEILINGS ARE
 NOT CONSIDERED PARTIONS AS DEFINED IN
 THE 2001 FBC CHAPTER 2.THE EXECPTIONS
 ALSO HAVE TO COMPLY WITH ALL FIVE
 REQUIREMENTS LISTED UNDER #2.
  
 SEE ALSO COMMENTS BY BUILDING & FIRE.
  