| Plan Review Notes For Permit 03051969 |
| Permit Number |
03051969 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-07-26 00:00:00 | PER CONVERSATION WITH MR. DON BOITNOTT | | | ON 7-28-03. | | | CORRIDOR 121 (FIRE EGRESS HALL) - | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | 1) A DETAIL OF THE WALL AND CEILING | | | ASSEMBLY.INDICATE WHERE THE WALL | | | RATING ENDS. | | | | | | 2) AS PER OUR CONVERSATION THIS IS A | | | DUCTED SYSTEM (NO PLENUM), PROVIDE DUCT | | | SIZE BETWEEN THE TRANSFER GRILLES. | | | | | | 3) CEILING FIRE DAMPERS REQUIRED AS PER | | | 2001 FBC(M) 607.2.PER OUR CONVERSATION | | | SECTION 705.1.2.2.1, EXCEPTIONS #2, | | | EXCEPTIONS EXPLAINED IN THIS SECTION ARE | | | FOR WALLS OR PARTITIONS.CEILINGS ARE | | | NOT CONSIDERED PARTIONS AS DEFINED IN | | | THE 2001 FBC CHAPTER 2.THE EXECPTIONS | | | ALSO HAVE TO COMPLY WITH ALL FIVE | | | REQUIREMENTS LISTED UNDER #2. | | | | | | SEE ALSO COMMENTS BY BUILDING & FIRE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|