| 2003-07-24 00:00:00 | THE INTENDED HORIZONTAL EXTENSION OF |
| | STAIR #122 DOES NOT COMPLY WITH FBC |
| | 705.1.3.2.1, TABLE 705.1.2 AND 705.1.3.4 |
| | IN THAT THE DOORS ENCLOSING THE "SHAFT |
| | EXTENSION" ARE SHOWN AS HAVING ONLY A 20 |
| | MINUTE RATING, AND SOME WITHOUT |
| | CLOSERS, FBC 705.1.3.2.3 AND 705.1.5. |
| | |
| | THE STAIR "SHAFT EXTENSION" DOES NOT |
| | COMPY WITH FBC 1006.1.3.1 IN THAT SHEET |
| | 602 SHOWS A MAJORITY OF THE A/C DUCT |
| | WORK TO BE LOCATED IN THE "SHAFT |
| | EXTENSION" AS WELL AS BEING USED FOR A |
| | RETURN AIR PLENUM.PLEASE REVISE AS |
| | NECESSARY. |
| | |
| | PLEASE PROVIDE A CONSTRUCTION DETAIL FOR |
| | THE PENETRATION PROTECTION METHOD OF |
| | THE BAR JOISTS PERPENDICULAR TO THE |
| | WALLS OF THE STAIR "SHAFT EXTENSION". |
| | SEE FBC 704.2.1.2 AND FBC 705.5.1. |
| | |
| | THE PREVIOUSLY REQUESTED |
| | CALCULATIONS FOR THE COMPONENTS AND |
| | CLADDING HAVE NOT BEEN PROVIDED.THE |
| | DELEGATED ENGINEER'S CALCULATIONS FOR |
| | THE METAL BUILDING DO NOT SHOW ANY |
| | INVESTIGATION FOR THE ROOF OR WALL |
| | SHEATHING. |
| | |
| | THE ARCHITECT WHO ASSUMED THE |
| | RESPONSIBILITY AS DESIGNER OF RECORD |
| | PROVIDED A NOTE ON SHEET 304 IN THE |
| | BLOCK TITLED "REQUIRED DESIGN |
| | PARAMETERS FOR WIND" AND DECLARES A |
| | MEAN ROOF HEIGHT AS "VARIES". |
| | THIS IS IN CONFLICT WITH ASCE 7-98 |
| | SECTION 6.5.6.3.1 THAT REQUIRES |
| | BUILDINGS OF 60' HEIGHT OR LESS TO USE |
| | VELOCITY PRESSURE Q SUB H WHICH IS |
| | DEFINED AS MEAN ROOF HEIGHT OR EAVE |
| | HEIGHT.ASCE 7-98 SECTION 6.3 |
| | |
| | THIS ISSUE IS EVEN MORE QUESTIONABLE |
| | WHEN THE DECLARED DESIGN PRESSURES ARE |
| | WITHIN 100THS OF 1 PSF OF THE NOA'S. |
| | |
| | THE INFORMATION PROVIDED FOR THE |
| | ALUMA-SHIELD WALL PANELS DOES NOT SHOW |
| | TESTING FOR ASTM E-136 TO DEMONSTRATE |
| | NON-COMBUSTIBLE (FBC 202) TO COMPLY |
| | WITH FBC 606 FOR TYPE IVCONSTRUCTION. |
| | |
| | THE L1 OF 1 USA SHEET DATED 7/9/03 |
| | NOTES THE ROOF AS UL 90 BUT IS MISSING |
| | THE UL CONSTRUCTION NUMBER. |
| | |
| | SITE PLAN SHEETS 101-105, AND THE FIRE |
| | ALARM PLANS, ARE NOT SIGNED, SEALED AND |
| | DATED. |