Plan Review Notes
Plan Review Notes For Permit 03051969
Permit Number 03051969
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS TO THE
 FLA. BLDG. CODE, CHAPTER 1,
 AMENDMENTS TO BLDG. ECT.
  
 1) CONTACT RODNEY COMPO, INDUSTRIAL PRE-
 TREATMENT, ENVIRONMENTAL COMPLIANCE FOR
 SIZING OF SAND/OIL INTECEPTOR. WASTE ORD
 # 2938-96. (561) 837-4074
 2) SUBMIT CALCULATION FOR MINIMUM FIX-
 TURE REQUIREMENTS PER TABLE 1003.1, AND
 TABLE 403.1.
 3) SHT 303 SHOW CLEAR FLOOR SPACE AND 5'
 TURINING CIRCLE PER SEC 11-4.22.3
 4) SHT 307 DETAIL #3, SHOWER - SHOW CON-
 TROL HEIGHT. 11-4.21.5, AND CURB SECTION
 11-4.21.2.7
 5) SHT 307 DETAILS #'S 7 & 8, SINKS
 SHALL COMPLY WITH 11-24 AND ALL SUB-
 SECTIONS. PLEASE SHOW ON DETAIL.
 6) SHT 307 DETAIL #9, DRINKING FOUNTAIN,
 PROVISIONS SHALL BE MADE FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING. SEC
 11-4.1.3(10).
 7) SHT 502 SANT. RISER DIAGRAM DOES NOT
 MEET CODE REQUIREMENTS. EWC IN REPAIR
 AREA #134 NOT VENTED. URNAL & LAV NOT
 VENTED IN MECH. BATH #106. EWC NOT VENT-
 ED OUTSIDE TOILET ROOMS #'S 125 & 126.
 8) SUBMIT A WATER RISER DIAGRAM.
 9) SUBMIT A COMPRESSED AIR RISER DIAGRAM
 10) SUBMIT A CONDENSATE RISER DIAGRAM.
 11) SHT 502 SUBMIT MANUF. INFO FOR SUMP
 PUMP. SEC 104.2.1 (FOR COMMENT # 8, 9,
 10, & 11).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692