Plan Review Notes
Plan Review Notes For Permit 03051969
Permit Number 03051969
Review Stop M
Sequence Number 1
Notes
Date Text
2003-06-10 00:00:00 
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.PLEASE CLARIFY PLAN SHEET 603 UNDER
 THE ASHRAE REQUIRMENTS ZONE A IS LISTED
 AS WAREHOUSE AND PLAN SHEET 302 SHOWS
 THIS SPACE REPAIR.THE REQUIREMENTS FOR
 A WAREHOUSE DIFFER FROM A REPAIR GARAGE.
 .05 CFM/SQ FT IS REQUIRED FOR A
 WAREHOUSE WHEREAS 1.5 CFM/PER SQ FT IS
 REQUIRED FOR A REPAIR GARAGE.
  
 2.PLEASE INDICATE WHAT WILL BE STORED
 IN ZONE B, (I.E. COMBUSTIBLES?)
  
 3.PLAN SHEET 601 - AIR CONDITIONING
 LEGEND DUCT SMOKE DETECTOR SEE NOTE 27,
 SHEET 603.THERE IS NOT A NOTE 27 ON
 SHEET 603.PLEASE CLARIFY.
  
 4.PLEASE NOTE DUCT SMOKE DETECTOR
 SHALL BE INSTALLED IN THE SUPPLY AS PER
 2001 FBC(M) 606.2.1.
  
 5.PLAN SHEET 502 INDICATES CONDENSATE
 AND OVERFLOW DRAINS THAT APPEAR TO RUN
 TOGETHER TO DRYWELL.AS PER 2001 FBC
 (M) 307.2.3 & 307.2.4, SECONDARY DRAIN
 TO TERMINATE AT A CONSPICUOUS POINT OR
 A FLOAT SWITCH WILL SUFFICE.