| Plan Review Notes For Permit 03051969 |
| Permit Number |
03051969 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-26 00:00:00 | 1) PLEASE INDICATE HOW FIRE AND | | | PARAMEDICAL EQUIPMENT ENTER THRU THE | | | SITE VARIOUS GATES. | | | | | | 2) FIRE HYDRANT AND NEW FIRE PROTECTION | | | LINE. PLEASE INDICATE SIZE OF LINE. | | | | | | 3) PLEASE EXPLAIN PURPOSE OF ALL THE | | | GATES. WHY ARE SO MANY GATES LOCATED | | | ON THE PROPERTY. | | | | | | 4) PLEASE PROVIDE MORE DETAILS ON OIL | | | TANKS. | | | | | | 5) PLEASE PROVIDE A LIFE SAFETY PLAN | | | INDICATING OCCUPANT LOADS, TRAVEL | | | DISTANCES, DEAD-ENDS, ETC. | | | | | | 6) WHAT ACTIVITIES WILL OCCUR WITHIN | | | REAIR 134. | | | | | | 7) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 8) SHAFTWAYS ARE TO BE MARKED. | | | | | | 9) PROVIDE SEPARATE PLANS FOR FIRE | | | ALARM SYSTEM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|