Plan Review Notes
Plan Review Notes For Permit 03051969
Permit Number 03051969
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-01 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 1WHAT ARE THE DOTTED LINES IN THE
 REPAIR #134 ON SHEET 301 INTENDED TO
 REPRESENT?
  
 2TWO EXITS ARE REQUIRED FROM REPAIR
 AREA #134 AS SHOWN ON SHEET 301.SEE
 FBC 1004.1.2 AND FBC 1004.1.4.
  
 3AS A CONSEQUENCE OF THE ABOVE
 CONDITION THE DISTANCE FROM THE
 MEZZANINE EXCEEDS 100' FOR GROUP S AS
 PROVIDED FOR IN FBC 1005.7.1.
  
 4STAIR #122 FROM THE SECOND FLOOR
 SHOWN ON SHEET 302 MUST DISCHARGE TO
 THE OUTSIDE OF THE BUILDING.SEE FBC
 1010.
  
 5SHEET 303.THE STAIRS FROM THE
 MECHANICAL ROOM #218 DO NOT COMPLY WITH
 FBC 1007.ALSO, THIS ROOM DOES NOT
 DEFINE AS A MEZZANINE IN ACCORDANCE
 WITH FBC 503.2.3.
  
 6HOW WERE THE PRESSURES FOR THE
 COMPONENTS AND CLADDING DETERMINED THAT
 ARE CALLED OUT ON SHEETS 304 AND 305?
 THE USA CALCULATIONS DO NOT SHOW AN
 INVESTIGATION FOR COMPONENTS AND
 CLADDING.PLEASE PROVIDE THE NECESSARY
 CALCULATIONS, INCLUDING THOSE FOR THE
 ROOF COVERING.NOTE THAT THE ROOF
 COVERING MUST BE DESIGNED TO MEET ONE
 OF STANDARDS IN FBC 1504.3 FOR THE WIND
 PRESSURES IN FBC 1606.
  
 7WHAT IS THE DESIGN LIVE LOAD FOR THE
 SECOND FLOOR OFFICE AREA?
  
 8SHEET L1 OF 1 OF THE USA PLANS
 DECLARES 100# LL FOR THE MEZZANINE.
 THE MINIMUM FOR LIGHT STORAGE IS 125#.
 PLEASE REVISE AS NECESSARY.SEE FBC
 TABLE 1604.
  
 9A NOTE ON SHEET 306 DECLARES THAT THE
 SKYLIGHTS ARE NOT REQUIRED TO BE
 MISSILE IMPACT RESISTANT.THAT IS
 INCORRECT.SEE FBC 2604.1.2.
  
 10SHEET 310.PLEASE PROVIDE DETAILS,
 SPECIFICATIONS FOR THE
 THREE INCH ALUMA-SHIELD PANELS.INCLUDE
 FIRE RESISTANCE AND WIND LOAD
 TEST DATA.SEE FBC 104.2.
  
 11PLEASE PROVIDE THE TEST DATA FOR
 THE EXPOSED VINYL FACED INSULATION IN
 THE METAL BUILDING.SEE FBC 708.3.
  
 12SHOW HOW THE VENTILATION RATE OF 1.5
 CFM / SQUARE FOOT WILL BE ACCOMPLISHED.
 SEE FBC 411.5.4 AND FBC TABLE M403.3
 FOR REPAIR GARAGES.
  
 13THE DOORS SHOWN IN THE SCHEDULE ON
 SHEET308 AS #9, #13 AND #33 ARE
 REQUIRED TO BE 90 MINUTE RATED AND
 LABLELED AND THOSE SHOWN AS #26 AND
 #62, 60 MINUTE LABLELED AND RATED.SEE
 FBC TABLE 705.1.2 FOR OCCUPANCY
 SEPARATIONS AND STAIRS RESPECTIVELY.
 SEE ALSO, FBC 411.5.3 RE: 9, 13, AND 33.
  
 14 SHEET LS-1 CITES THE WRONG EDITION
 OFTHE LIFE SAFETY CODE.SEE THE
 FLORIDA FIRE PREVENTION CODE.
  
 15LS-1, PLEASE CITE THE CITY OF WEST
 PALM BEACH AMENDMENTS TO THE FBC, NOT
 LAKE PARK.
  
 16SHEET 401, FOUNDATION NOTES
 DECLARES CONCRETE DESIGN TO ACI 301-72,
 SEE FBC 1901.1 AND FBC 3502 FOR THE
 CURRENT EDITION OF ACI 318 AND ENSURE
 COMPLIANCE WITH SAME.
  
 17NOA 01-08283.07 FOR THE ROLL UP
 DOORS HAS ILLEGIBLE PAGES.NOA
 00-0508.4 FOR THE KAWNEER DOOR IS
 EXPIRED.
  
 18PLEASE PROVIDE AN ISTALLATION
 SCHEDULE FOR THE SHUTTERS TO BE USED
 INCLUDINGLOCATIONS, SIZES, SPANS,
 FASTENERS AND ANY OTHER PERTINENT
 INFORMATION.
  
 19SECTION 10/318 WINDOW SECTION.
 SHOWTHE METHOD OF FRAMING, BLOCKING,
 ETC THAT WILL EXCEPT THE WINDOWS AND
 DOORS.FBC 104.2.
  
 THE ENERGY CODE IS REQUIRED TO BE SIGNED
 AND SEALED AND PREPARED FOR THE CITY OF
 WEST PALM BEACH JURISDICTION 0604700.
 SEE FBC 13-103.1.1.1.