| 2003-07-01 00:00:00 | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, THE PERMIT PLANS STAMPED |
| | BY THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |
| | |
| | 1WHAT ARE THE DOTTED LINES IN THE |
| | REPAIR #134 ON SHEET 301 INTENDED TO |
| | REPRESENT? |
| | |
| | 2TWO EXITS ARE REQUIRED FROM REPAIR |
| | AREA #134 AS SHOWN ON SHEET 301.SEE |
| | FBC 1004.1.2 AND FBC 1004.1.4. |
| | |
| | 3AS A CONSEQUENCE OF THE ABOVE |
| | CONDITION THE DISTANCE FROM THE |
| | MEZZANINE EXCEEDS 100' FOR GROUP S AS |
| | PROVIDED FOR IN FBC 1005.7.1. |
| | |
| | 4STAIR #122 FROM THE SECOND FLOOR |
| | SHOWN ON SHEET 302 MUST DISCHARGE TO |
| | THE OUTSIDE OF THE BUILDING.SEE FBC |
| | 1010. |
| | |
| | 5SHEET 303.THE STAIRS FROM THE |
| | MECHANICAL ROOM #218 DO NOT COMPLY WITH |
| | FBC 1007.ALSO, THIS ROOM DOES NOT |
| | DEFINE AS A MEZZANINE IN ACCORDANCE |
| | WITH FBC 503.2.3. |
| | |
| | 6HOW WERE THE PRESSURES FOR THE |
| | COMPONENTS AND CLADDING DETERMINED THAT |
| | ARE CALLED OUT ON SHEETS 304 AND 305? |
| | THE USA CALCULATIONS DO NOT SHOW AN |
| | INVESTIGATION FOR COMPONENTS AND |
| | CLADDING.PLEASE PROVIDE THE NECESSARY |
| | CALCULATIONS, INCLUDING THOSE FOR THE |
| | ROOF COVERING.NOTE THAT THE ROOF |
| | COVERING MUST BE DESIGNED TO MEET ONE |
| | OF STANDARDS IN FBC 1504.3 FOR THE WIND |
| | PRESSURES IN FBC 1606. |
| | |
| | 7WHAT IS THE DESIGN LIVE LOAD FOR THE |
| | SECOND FLOOR OFFICE AREA? |
| | |
| | 8SHEET L1 OF 1 OF THE USA PLANS |
| | DECLARES 100# LL FOR THE MEZZANINE. |
| | THE MINIMUM FOR LIGHT STORAGE IS 125#. |
| | PLEASE REVISE AS NECESSARY.SEE FBC |
| | TABLE 1604. |
| | |
| | 9A NOTE ON SHEET 306 DECLARES THAT THE |
| | SKYLIGHTS ARE NOT REQUIRED TO BE |
| | MISSILE IMPACT RESISTANT.THAT IS |
| | INCORRECT.SEE FBC 2604.1.2. |
| | |
| | 10SHEET 310.PLEASE PROVIDE DETAILS, |
| | SPECIFICATIONS FOR THE |
| | THREE INCH ALUMA-SHIELD PANELS.INCLUDE |
| | FIRE RESISTANCE AND WIND LOAD |
| | TEST DATA.SEE FBC 104.2. |
| | |
| | 11PLEASE PROVIDE THE TEST DATA FOR |
| | THE EXPOSED VINYL FACED INSULATION IN |
| | THE METAL BUILDING.SEE FBC 708.3. |
| | |
| | 12SHOW HOW THE VENTILATION RATE OF 1.5 |
| | CFM / SQUARE FOOT WILL BE ACCOMPLISHED. |
| | SEE FBC 411.5.4 AND FBC TABLE M403.3 |
| | FOR REPAIR GARAGES. |
| | |
| | 13THE DOORS SHOWN IN THE SCHEDULE ON |
| | SHEET308 AS #9, #13 AND #33 ARE |
| | REQUIRED TO BE 90 MINUTE RATED AND |
| | LABLELED AND THOSE SHOWN AS #26 AND |
| | #62, 60 MINUTE LABLELED AND RATED.SEE |
| | FBC TABLE 705.1.2 FOR OCCUPANCY |
| | SEPARATIONS AND STAIRS RESPECTIVELY. |
| | SEE ALSO, FBC 411.5.3 RE: 9, 13, AND 33. |
| | |
| | 14 SHEET LS-1 CITES THE WRONG EDITION |
| | OFTHE LIFE SAFETY CODE.SEE THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 15LS-1, PLEASE CITE THE CITY OF WEST |
| | PALM BEACH AMENDMENTS TO THE FBC, NOT |
| | LAKE PARK. |
| | |
| | 16SHEET 401, FOUNDATION NOTES |
| | DECLARES CONCRETE DESIGN TO ACI 301-72, |
| | SEE FBC 1901.1 AND FBC 3502 FOR THE |
| | CURRENT EDITION OF ACI 318 AND ENSURE |
| | COMPLIANCE WITH SAME. |
| | |
| | 17NOA 01-08283.07 FOR THE ROLL UP |
| | DOORS HAS ILLEGIBLE PAGES.NOA |
| | 00-0508.4 FOR THE KAWNEER DOOR IS |
| | EXPIRED. |
| | |
| | 18PLEASE PROVIDE AN ISTALLATION |
| | SCHEDULE FOR THE SHUTTERS TO BE USED |
| | INCLUDINGLOCATIONS, SIZES, SPANS, |
| | FASTENERS AND ANY OTHER PERTINENT |
| | INFORMATION. |
| | |
| | 19SECTION 10/318 WINDOW SECTION. |
| | SHOWTHE METHOD OF FRAMING, BLOCKING, |
| | ETC THAT WILL EXCEPT THE WINDOWS AND |
| | DOORS.FBC 104.2. |
| | |
| | THE ENERGY CODE IS REQUIRED TO BE SIGNED |
| | AND SEALED AND PREPARED FOR THE CITY OF |
| | WEST PALM BEACH JURISDICTION 0604700. |
| | SEE FBC 13-103.1.1.1. |