| Date |
Text |
| 2003-07-07 00:00:00 | |
| | *** ISSUED PERMIT*** |
| | -PLAN REVIEW HISTORY- |
| | |
| | PERMIT# 03051869 |
| | ADDRESS: 2355 MORGANS BLUFF |
| | CONT: SIERRA CONSTRUCTION |
| | TELL # (786)236-5362 |
| | |
| | THE ATTACHED COMMENTS ARE PART OF THE |
| | PERMIT AND PLAN REVIEW PACKAGE AND ARE |
| | NOT TO BE REMOVED FROM THE ISSUED SET OF |
| | PLANS.104.2.1.2 ADMINISTRATIVE CODE. |
| | |
| | *****PROVISO****** |
| | |
| | 1)R-3 EGRESS DOOR/ 32" CLEAR: |
| | 1003.2.1. THE WIDTH OF THE MEANS OF |
| | EGRESS SHALL BE DETERMINED FROM THE |
| | OCCUPANTS SERVED IN ACCORDANCE WITH |
| | TABLE 1004.R-3 MINIMUM CLEAR OPENING OF |
| | EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS |
| | USED IN THE EXIT ACCESS SHALL PROVIDE A |
| | CLEAR OPENING OF NOT LESS THAN 32" WIDE. |
| | 1012.1.7 REQUIRED EXIT DOORS SHALL BE |
| | OPENABLE FROM THE INSIDE WITHOUT THE USE |
| | OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR |
| | EFFORT. MANUALLY OPERATED FLUSH BOLTS OR |
| | SURFACE BOLTS ARE PROHIBITED. ALL HARD- |
| | WARE MUST BE DIRECT ACTING REQUIRING NO |
| | MORE THAN ONE OPERATION. |
| | |
| | REVIEW FRONT ENTRY, REVISE BEFORE BUCK |
| | INSPECTION. |
| | |
| | 2) STORM SHUTTERS: |
| | A) MISSING KEY PLAN |
| | B) BOTTOM FASTENER, CAULK-IN, THE VALUE |
| | TAKEN FOR CONCRETE, NOT CEMENT BLOCK, |
| | OR IF THIS VALUE IS TO BE TAKEN FOR |
| | FILLED CELL THE CAULK-IN MUST BE SET IN |
| | 2500 PSI CONCRETE. OTHER ALTERNATIVE IS |
| | A DIFFERENT FASTENER FOR BLOCK. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 805-6715 |