| | R-3 EGRESS DOOR/ 32" CLEAR: |
| | 1003.2.1. THE WIDTH OF THE MEANS OF |
| | EGRESS SHALL BE DETERMINED FROM THE |
| | OCCUPANTS SERVED IN ACCORDANCE WITH |
| | TABLE 1004.R-3 MINIMUM CLEAR OPENING OF |
| | EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS |
| | USED IN THE EXIT ACCESS SHALL PROVIDE A |
| | CLEAR OPENING OF NOT LESS THAN 32" WIDE. |
| | 1012.1.7 REQUIRED EXIT DOORS SHALL BE |
| | OPENABLE FROM THE INSIDE WITHOUT THE USE |
| | OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR |
| | EFFORT. MANUALLY OPERATED FLUSH BOLTS OR |
| | SURFACE BOLTS ARE PROHIBITED. ALL HARD- |
| | WARE MUST BE DIRECT ACTING REQUIRING NO |
| | MORE THAN ONE OPERATION. |
| | |
| | REVIEW FRONT ENTRY REVISE BEFORE BUCK |
| | INSPECTION. |
| | |
| | 2) STORM SHUTTERS : |
| | A) MISSING KEY PLAN THAT TIES TO THE |
| | INSTALLATION SCHEDULE. |
| | B) BOTTOM FASTENER CAULK-IN, THE VALUE |
| | TAKEN IS FOR CONCRETE, NOT CEMENT BLOCK! |
| | THIS FASTENER MAY NOT BE USED IN BLOCK, |
| | OR IF THIS IS USED IN FILLED CELL, THE |
| | CAULK-IN MUST BE IN 2500 PSI CONCRETE |
| | (FILED CELL).OTHER ALLTERNATIVE IS A |
| | DIFFERENT FASTENER FOR BLOCK! |
| | |
| | BUILDING PLAN REVIEW |