| Plan Review Notes For Permit 03051835 |
| Permit Number |
03051835 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-07-07 00:00:00 | ****PROVISO****** | | | 1)R-3 EGRESS DOOR/ 32" CLEAR: | | | 1003.2.1. THE WIDTH OF THE MEANS OF | | | EGRESS SHALL BE DETERMINED FROM THE | | | OCCUPANTS SERVED IN ACCORDANCE WITH | | | TABLE 1004.R-3 MINIMUM CLEAR OPENING OF | | | EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS | | | USED IN THE EXIT ACCESS SHALL PROVIDE A | | | CLEAR OPENING OF NOT LESS THAN 32" WIDE. | | | 1012.1.7 REQUIRED EXIT DOORS SHALL BE | | | OPENABLE FROM THE INSIDE WITHOUT THE USE | | | OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR | | | EFFORT. MANUALLY OPERATED FLUSH BOLTS OR | | | SURFACE BOLTS ARE PROHIBITED. ALL HARD- | | | WARE MUST BE DIRECT ACTING REQUIRING NO | | | MORE THAN ONE OPERATION. | | | | | | 2) STORM SHUTTERS: | | | A) MISSING KEY PLAN | | | B) BOTTOM FASTENER CAULK-IN, THE VALUE | | | TAKEN IS FOR CONCRETE, NOT CEMENT BLOCK! | | | THIS FASTENER MAY NOT BE USED IN BLOCK, | | | OR IF THIS IS USED IN FILLED CELL, THE | | | CAULK-IN MUST BE IN 2500 PSI CONCRETE | | | (FILLED CELL). OTHER ALTERNATIVE IS A | | | DIFFERENT FASTENER FOR BLOCK. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|