| Plan Review Notes For Permit 03051826 |
| Permit Number |
03051826 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-07-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 AMENDMENTS, CHAPTER | | | ONE, ADMID. CODE | | | | | | 1) THE SANITARY RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN NOR DOES IT MEET | | | CODE REQUIREMENTS. | | | 2) BATH #3 SHOW 4 LAVS ON RISER AND ONLY | | | 2 ON THE FLOOR PLAN. | | | 3) BATH #4, ONLY THE FIXTURES IN THE | | | BATHROOM GROUP SHALL CONNECT TO THE WET- | | | VENTED HORIZONTAL BRANCH DRAIN. A SEPAR- | | | ATE STACK FOR BAR SINK SHALL TIE IN | | | DOWNSTREAM OF THE BATHROOM FIXTURES. | | | SECTION 909.1 | | | 4) BATH #1 FROM PREVIOUS REVIEW, THE | | | LAUNDRY SINK AND WASH MACHINE SHALL TIE | | | IN DOWNSTREAM OF THE BATHROOM FIXTURES. | | | SECTION 909.1. ALSO SEE ATTACHED SHEET | | | TO PREVIOUS REVIEW FOR EXAMPLE OF HOW | | | THE LAUNDRY ROOM/BATHROOM #1 SHOULD BE | | | PIPED FOR CODE COMPLIANCE AND TO REFLECT | | | THE FLOOR PLAN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|