| Plan Review Notes For Permit 03051826 |
| Permit Number |
03051826 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-16 00:00:00 | DENIED: | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 1.RETURN AIR - PLEASE PROVIDE GRILLE | | | SIZES AND SIZE OF DUCTWORK.PLAN SHEET | | | M3 AIR TERMINAL SCHEDULE, R/A "SEE SHEET | | | FOR SIZES" - GRILLE SIZES ARE NOT SHOWN. | | | | | | 2.EXHAUST FANS ARE NOT IDENTIFIED AS | | | PER SCHEDULE INDICATED ON PLAN SHEET M3. | | | | | | 3.PLEASE PROVIDE OUTSIDE AIR CALCS BY | | | BY NATURAL MEANS (2001 FBC(M) 402.2) OR | | | BY MECHANICAL MEANS (2001 FBC(M) TABLE | | | 403.3). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|