| Plan Review Notes For Permit 03051812 |
| Permit Number |
03051812 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 AMENDMENTS, CHAPTER | | | ONE | | | FLORIDA ADMINISTRATIVE CODE | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. | | | A) A STANDPIPE IS REQUIRED FOR WASH | | | MACHINE. SECTION 802.4 | | | B) A TRAP IS REQUIRED FOR WASH MACHINE. | | | SECTION 1002.1 | | | C) LAUNDRY SINK IS NOT VENTED. SECTION | | | 901.2.1 | | | 2) 61G1-16.004 ARCHITECT'S LICENSE IS | | | REQUIRED ON EACH SHEET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|