2003-09-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 AND RESUBMIT FOR REVIEW.
  
 CORRECT THE ARCHITECTS TITLE BLOCK TO
 COMPLY WITH 61G1-16.004.
  
 THE RISER DIAGRAM SHOWS THE PANEL BEING
 FED FROM THE METER AND THE PLAN
 INDICATES A METER MAIN,PLEASE CORRELATE.
  
 THE RECEPTACLE IN THE POWDER ROOM MUST
 BE GFI PROTECTED PER 210.8(A)(1).
  