Plan Review Notes
Plan Review Notes For Permit 03051730
Permit Number 03051730
Review Stop P
Sequence Number 2
Notes
Date Text
2003-06-21 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 0) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED.
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) 61G15-23.002(2) ENGINEER SHALL LEGIB-
 LY INDICATE THEIR NAME, ADDRESS, AND
 NUMBER (ENG. FIRM NUMBER) ON EACH SHEET.
 A TITLE BLOCK ON EACH SHEET WITH ABOVE
 INFORMATION WILL SATISFY THIS REQUIRE-
 MENT.
 **NEW COMMENT**
 SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 553.80(2)(B)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692