Plan Review Notes
Plan Review Notes For Permit 03051730
Permit Number 03051730
Review Stop P
Sequence Number 1
Notes
Date Text
2003-05-30 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FLA. STATUTES.
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) 61G15-23.002(2) ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND NUMBER ON EACH SHEET. A TITLE BLOCK
 ON EACH SHEET WITH ABOVE INFORMATION
 WILL SATISFY THIS REQUIREMENT.
  