| Plan Review Notes For Permit 03051683 |
| Permit Number |
03051683 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-30 00:00:00 | DENIED | | | REFERENCE: FLORIDA STATUTES. | | | | | | 1) 61G1-16.003 THE PERSONAL SEAL, SIG- | | | NATURE AND DATE OF THE ARCHITECT SHALL | | | APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO | | | BE FILED FOR PUBLIC RECORD. | | | 2) 61G1-16.004(2) FIRM LICENSE NUMBER | | | REQUIRED ON TITLE BLOCK. | | | 3) 2" DRAIN REQUIRED FOR SHOWER. IF ONLY | | | 1-1/2" DRAIN IS AVAILABLE, A LETTER FROM | | | AN ENGINEER, SIGNED AND SEALED, INDICAT- | | | ING THAT THE 1-1/2" DRAIN WILL BE SUFFI- | | | CIENT SHALL BE REQUIRED ON THE JOBSITE | | | AT TIME OF ROUGH INSPECTION. LETTER | | | SHALL BE DATED AND HAVE A TITLE BLOCK | | | COMPLYING WITH 61G15-23.002(2). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|