2003-05-30 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES.
  
 1) 61G1-16.003 THE PERSONAL SEAL, SIG-
 NATURE AND DATE OF THE ARCHITECT SHALL
 APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO
 BE FILED FOR PUBLIC RECORD.
 2) 61G1-16.004(2) FIRM LICENSE NUMBER
 REQUIRED ON TITLE BLOCK.
 3) 2" DRAIN REQUIRED FOR SHOWER. IF ONLY
 1-1/2" DRAIN IS AVAILABLE, A LETTER FROM
 AN ENGINEER, SIGNED AND SEALED, INDICAT-
 ING THAT THE 1-1/2" DRAIN WILL BE SUFFI-
 CIENT SHALL BE REQUIRED ON THE JOBSITE
 AT TIME OF ROUGH INSPECTION. LETTER
 SHALL BE DATED AND HAVE A TITLE BLOCK
 COMPLYING WITH 61G15-23.002(2).
  
 REVIEW BY KEN STEVENS