| Plan Review Notes For Permit 03051683 |
| Permit Number |
03051683 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-23 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE ADDRESS THE FOLLOWING COMMENTS | | | AND RESUBMIT FOR REVIEW. | | | | | | 1} ADD A RECEPTACLE TO IN THE BEDROOM TO | | | COMPLY WITH 210-52(A)(1). | | | | | | 2} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12. | | | | | | NOTE: PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | NOTE: PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENGINEER | | | OF RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|