| Date |
Text |
| 2003-07-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 AMENDMENTS, CHAPTER |
| | ONE, ADMIN. CODE |
| | FLORIDA STATUTES. |
| | |
| | A) MOST COMMENTS FROM ORIGINAL REVIEW |
| | HAVE NOT BEEN ADDRESSED. ORIGINAL NUMBER |
| | SHALL BE SHOWN FOR CLAIRITY. |
| | 1) ROUTE PLANS TO THE PALM BEACH COUNTY |
| | HEALTH UNIT DIVISION OF ENVIRONMENTAL |
| | HEALTH, 901 EVERNIA ST. W.P.B. FOR RE- |
| | VIEW PRIOR TO RESUBMITTING TO THE CITY |
| | FOR PLAN REVIEW. SEC 101.4.7 |
| | 3) SHT A-9 SECTION 11-4.22.4 WHERE 6 OR |
| | MORE STALLS ARE PROVIDED, IN ADDITION TO |
| | THE STALL COMPLYING WITH 11-4.17.3, AT |
| | LEAST ONE STALL 36" WIDE WITH AN OUTWARD |
| | SWINGING, SELF-CLOSING DOOR AND PARALLEL |
| | GRAB BARS COMPLYING WITH FIGURE 30(D) & |
| | 11-4.26 SHALL BE PROVIDED. |
| | 4) SHT P-1 MAIN HIP HOP BAR, NO SANT. |
| | DRAIN LINE SHOWN FOR HAND SINK. ALSO NO |
| | SANT. DRAIN LINE SHOWN FOR ICE MACHINES. |
| | PLEASE CLAIRFY. SECTION 104.2.1 |
| | 5) SHTS P-1 & P-3 CLEANOUT BY BAR #2 |
| | SHALL CLEAN IN THE DIRECTION OF FLOW. |
| | SEE RED LINE CORRECTIONS ON FLOOR PLAN & |
| | SANITARY RISER DIAGRAM. SEC 708.3.3 |
| | 6) SHT P-2 NO WATER SHOWN FOR THE ICE |
| | MACHINES. PLEASE CLAIRFY. SEC 104.2.1 |
| | 7) SHT P-2 GENERAL PLUMBING NOTES: |
| | #11 CONDENSATE SHALL RUN SEPARATELY OUT |
| | OF THE BLDG AND TIE INTO STORM, A CATCH |
| | BASIN, OR A DRYWELL. UTILITY ORDINANCE |
| | 90-125(5) |
| | #12 AIR CHAMBERS ARE NOT APPROVED. DE- |
| | LETE FROM REFERENCE. SEC 604.9 |
| | 8) SHT P-4 ELECTRIC WATER HEATER DETAIL, |
| | EMERGENCY PAN REQUIRED SEC 504.8. THERM- |
| | AL EXPANSION CONTROL REQUIRED. SECTION |
| | 607.3.2 |
| | 9) SHT P-4 WATER RISER ISOMETRIC, AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | RISER DIAGRAM. WATER HAMMER ARRESTORS |
| | SHALL BE LOCATED IN AN "EFFECTIVE RANGE" |
| | NEAR THE FIXTURES NOT IN THE CEILING AT |
| | THE TOP OF THE DROPS. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | 10) SHT P-4 WATER HEATER FOR PRIVATE |
| | BATHROOM, T/P RELIEF VALVE SHALL DRAIN |
| | TO A FLOOR SINK OR A HUB DRAIN. FUNNEL |
| | DRAINS ARE NOT APPROVED. SEC'S 802.3 & |
| | 802.3.2 |
| | NEW COMMENTS....... |
| | 11) ONLY ONE FULL SET OF PLANS HAS BEEN |
| | SUBMITTED. OTHER ROLL OF PLANS HAVE ONLY |
| | A2, A3, A4, A8, & A9 SHEETS. SUBMIT TWO |
| | COMPLETE SETS OF PLANS. |
| | 12) SEE ATTACHED SHEET CONCERNING |
| | FLORIDA STATUTE 553.80(2)(B) DESIGN |
| | PROFESSIONAL DOCUMENTS. NEXT REVIEW WILL |
| | BE THE THIRD REVIEW. FIRST TWO HAVE THE |
| | SAME COMMENTS. |
| | ---------WHEN RESUBMITTING PLANS-------- |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |