2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 SHALL BE REQUIRED. INDICATE IF A DRINK-
 ING FOUNTAIN IS LOCATED IN THE COMMON
 AREA.
 2) SHT MP-1 WATER HEATER DETAIL. RELIEF
 VALVE DISCHARGE PIPE SHALL NOT TIE INTO
 THE DRAIN PIPE FOR THE EMERGENCY PAN FOR
 HEATER. 504.7.1 - A VISIBLE AIR GAP IS
 REQUIRED.
  