| Date |
Text |
| 2003-05-30 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - EXTERIOR WINDOWS |
| | - EXTERIOR DOORS |
| | - OVERHEAD GARAGE DOOR |
| | |
| | 3) THE FBC 1606.1.4 REQUIRES GLAZED |
| | OPENINGS IN WINDBOURNE DEBRIS REGIONS TO |
| | BE IMPACT RESISTANT OR PROTECTED WITH |
| | IMPACT RESISTANT COVERINGS. |
| | PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | |
| | 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 5) SPECIFY THE INSULATION FOR THE WALLS |
| | AND ATTIC OF THE HABITABLE SPACE. FBC |
| | CHAPTER 13 REQUIRES THE COMPONENTS BEING |
| | REPLACED OR RETROFITTED TO COMPLY WITH |
| | ENERGY CODE. |
| | |
| | 6) OPENINGS FROM A GARAGE DIRECTLY INTO |
| | A ROOM USED FOR SLEEPING PURPOSES IS NOT |
| | PERMITED PER FBC 411.2.8. |
| | |
| | 7) INDICATE THE POSITIVE AND NEGATIVE |
| | DESIGN WIND PRESSURES FOR THE NEW DOOR |
| | THAT WAS DRAWN IN. |
| | |
| | 8) ITEMS THAT WERE ADDED (DRAWN IN) TO |
| | THE PLANS ARE REQUIRED TO BY INITIALED |
| | AND DATED BY THE DESIGNER OF RECORD. |
| | |
| | 9) INDICATE ON THE PLAN THAT ADEQUATE |
| | SUBSTRATE WILL BE PROVIDED FOR THE |
| | ATTACHMENT OF THE HURRICANE PANELS. |
| | |
| | 10) REVIEW PLANS FOR SHEARWALL |
| | COMPLIANCE PER FBC 2313. SPECIFY THE |
| | NAIL SIZE AND SPACING FOR SHEAR WALL |
| | PANELS PER FBC 2310.4. |
| | |
| | 11) IF WIRE MESH IS USED IN THE SLAB IT |
| | IS REQUIRED TO BE SUPPORTED ON APPROVED |
| | MATERIAL AT A MAXIMUM OF THREE FEET O.C. |
| | PER FBC 1909.3. |
| | |
| | 12) THE NAIL SPACING FOR THE ROOF |
| | SHEATHING HAS 6" THROUGHOUT IN ONE NOTE |
| | AND 4"EDGES & 6" IN THE FIELD IN ANOTHER |
| | PLEASE CORRECT. |
| | |
| | 13) SPECIFY THAT A 3"X3" WASHER IS |
| | REQUIRED ON THE 1/2" ANCHOR BOLTS. |
| | |
| | 14) SPECIFY THE CONNECTOR THAT WILL BE |
| | USED TO ATTACH THE BOTTOM PLATE TO THE |
| | STUDS IN ORDER TO CREATE A CONTINOUS |
| | LOAD PATH FROM THE ROOF TO FOUNDATION |
| | PER FBC 1606.1.3. |
| | |
| | 15) THE UPLIFT VALUE IN THE TRUSS ANCHOR |
| | SCHEDULE FOR THE (2) HTS-20 CONNECTORS |
| | IS INCORRECT. THE VALUE SHOULD BE 2900# |
| | (1450# EACH STRAP) PER 2003 SIMPSON |
| | CATALOG. |
| | |
| | 16) NOTES UNDER WOOD FRAME CONSTRUCTION |
| | ON SHEET 1 SPECIFIES 8D COMMON OR HOT |
| | DIPPED GAL. NAILS AND NOTE ON SHEET 8 |
| | CALLS FOR 8D RING SHANK NAILS FOR ROOF |
| | SHEATHING ATTACHMENT. PLEASE CLARIFY. |
| | |
| | 17) PLEASE CLARIFY IF THE 3" SCREEN VENT |
| | AT THE SOFFIT IS CONTINOUS. |
| | |
| | 18) SHEETS 2 THROUGH 7 OF THE DRAWINGS |
| | ARE MISSING. PLEASE CLARIFY. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |