| Plan Review Notes For Permit 03051563 |
| Permit Number |
03051563 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-18 00:00:00 | PASS PRIVISO | | | SECTION 610.1.ABC.3.5.2 2001 ENERGY CODE | | | AIR HANDLERING UNITS SHALL BE ALLOWED | | | IN ATTICS IF FOLLOWINGS CONDITIONS ARE | | | MET. | | | 1) THE SERVICE PANEL OF THE EQUIPMENT IS | | | LOCATED WITHIN 6FT.OF ATTIC ACCESS. | | | 2) A DEVICE IS INSTALLED TO ALERT OWNER | | | OR SHUT UNIOT DOWN WHEN CONDENSATION | | | DRAIN IS NOT WORKING PROPERLY. | | | 3) THE ATTIC ACCESS OPENING IS OF SUFFIC | | | IENT SIZE YO REPLACE AIRHANDLER | | | 4) A NOTE IS POSTED ON THE ELECTRIC | | | SERVICE PANEL INDICATING THE HOMEOWNER | | | THAT THE AIRHANDLER IS LOCATED IN THE | | | ATTIC. | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|