| Plan Review Notes For Permit 03051515 |
| Permit Number |
03051515 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FBC-2001 ADMIN. CODE, CHAPTER | | | 1 AND AMENDMENTS | | | | | | 1) SUBMIT A SANITARY RISER DIAGRAM AND A | | | WATER RISER DIAGRAM. SEC 104.2.1 | | | 2) PROVIDE DETAIL FOR HDCP TOILET ROOM | | | PER SEC 11-4.22 | | | 3) INDICATE WIDTH OF TOILET ROOM FOR THE | | | SECTION AT THE WATER CLOSET AND LAV. | | | MINIMUM OPENING FOR W/C AND LAV SHALL BE | | | 5'3". SEC 405.3.1 | | | SHOW CLEAR FLOOR SPACE FOR W/C AND LAV. | | | 4) TABLE 403.1 REQUIRES A DRINKING | | | FOUNTAIN. (ALSO SEE SEC 410.1) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|