| 2003-05-23 00:00:00 | DENIED: | | | | | | 1.PLEASE PROVIDE OUTSIDE AIR CALCS AS | | | PER 2001 FBC(M) TABLE 403.3. | | | | | | 2.PLEASE NOTE THE PROXIMITY OF THE | | | OUTSIDE AIR INTAKE TO THE CONDENSING | | | UNIT. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE AS PER | | | 2001 FBC(M) 606.2.1 & NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|