Plan Review Notes
Plan Review Notes For Permit 03051515
Permit Number 03051515
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-21 00:00:00***************** UNSAT ***************
  
 PLEASE NOTE, PLANS ARE NOT COMPLETE AT
 THIS TIME THERE MAY BE OTHER COMMENTS.
 PLEASE SEE COMMENTS BELOW AND ADDRESS.
  
 1)NOTE: PLEASE CORRELATE PLAN W/ RISER
 DIAGRAM. PLAN SHOWS NEW 150A PANEL,
 RISER SHOWS NEW 200A DISC FEEDING EXIST-
 ING 150A PANEL? PANEL SCHEDULE SHOWS
 AS 200A PANEL?? ETC
  
 2)NOTE: RISER SHOWS A NEW 200A DISC
 BEING ADDED BY PLACING DOUBLE LUGS ON
 EXISTING METERCAN. PLEASE SHOW LOAD
 ON EXISTING METER, SERVICE ENTRANCE
 CONDUCTOR SIZE FOR NEW LOAD. PLEASE ALSO
 SHOW SIZE OF METERCAN? 215-5
  
 3)NOTE: PLEASE SEE 310-16 FOR SIZING
 OF NEW FEEDERS. SHOWS 1/0` FOR 200A DISC
 ?
  
 4)NOTE; PLEASE SEE 250-24. AN EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISC. SHOWS
 FROM METER TO MAIN ALSO.
  
 5)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE.
 PLEASE SEE 700-12E FOR EM/ EXT LTS AND
 CIRCUITING.
  
 6)NOTE: PLEASE SEE THAT PLANS ARE SHOWN
 AS BLANK FOR NEW LIGHTING??
  
 7)NOTE: PLEASE CLARFIY IF BATH GFI
 RECEPT IS ON W/ BATH LT CIRCUIT? SHOWN
 AS #14, 15A?
  
 8)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215-3/ 230-42 ETC
  
 PLEASE SUBMIT ALL OF THE ABOVE INFORMAT-
 -ION FOR REVIEW. PLEASE REMOVE OLD/VOID-
 ED SHEETS AND INSERT NEW INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]