2003-06-03 00:00:00BUILDING PLAN REVIEW
 PERMIT:03051469
 ADD: 901 S FLAGLER
 CONT: KEVIN ADAIR
 TEL: (561)714-5259
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 DOOR INTO SPACE 1282 DOES NOT MEET
 THE MANEUVERING CLEARENCES ON EITHER THE
 PUSH OR PULL SIDE.
  
 2) DORS INTO SPACES 1279 & 1280 LOOK AS
 TO HAVE SIDE LIGHTS, 2405.2 HAZARDOUS
 LOCATION, SAFETY GLASS REQUIRED.
  
 3)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)805-6715