| Plan Review Notes For Permit 03051415 |
| Permit Number |
03051415 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-1 PLEASE SHOW CLEAR FLOOR SPACE | | | FOR WOMEN'S HDCP STALL, (#105), AND MENS | | | HDCP STALL, (#120) PER SECTION 11-4.22.3 | | | 2) SHT PB-1 PLUMBING NOTES #5, AIR CHAM- | | | BERS ARE NOT APPROVED. PLEASE DELETE RE- | | | FERENCE. | | | 3) SEPARATE GAS PERMIT REQUIRED. | | | 4) SHT PD-1 ANY PLUMBING PIPING DEMO'ED | | | SHALL BE INSPECTED PRIOR TO COVERING. | | | 5) SHT P-1 SINK P-7 IN LOUNGE, (#115), | | | SHALL COMPLY WITH SECTION 11-4.24 & ALL | | | SUBSECTIONS. PLEASE PROVIDE A DETAIL. | | | 6) SHT P-1 KEYNOTES #11, NEW FILTERS | | | SHALL BE NSF APPROVED. PLEASE SUBMIT | | | MANUF. INFORMATION. | | | 7) SHT P-2 WATER RISER ISOMETRIC, ALL | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURES, IN AN "EFFICTIVE | | | RANGE", NOT IN THE CEILING AT THE TOP OF | | | THE DROPS. PDI-WH 201 & MANUF. INSTALL- | | | ATION INSTRUCTIONS. | | | 8) SHT P-5 DETAIL 8/P-5, CONDENSATE TRAP | | | DETAIL. FLOOR DRAIN NOT AN APPROVED IN- | | | DIRECT WASTE RECEPTOR. FLOOR SINK OR HUB | | | DRAIN REQUIRED. SECTIONS 802.3 & 802.3.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|