Plan Review Notes For Permit 03051415
Permit Number 03051415
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 PLEASE SHOW CLEAR FLOOR SPACE
 FOR WOMEN'S HDCP STALL, (#105), AND MENS
 HDCP STALL, (#120) PER SECTION 11-4.22.3
 2) SHT PB-1 PLUMBING NOTES #5, AIR CHAM-
 BERS ARE NOT APPROVED. PLEASE DELETE RE-
 FERENCE.
 3) SEPARATE GAS PERMIT REQUIRED.
 4) SHT PD-1 ANY PLUMBING PIPING DEMO'ED
 SHALL BE INSPECTED PRIOR TO COVERING.
 5) SHT P-1 SINK P-7 IN LOUNGE, (#115),
 SHALL COMPLY WITH SECTION 11-4.24 & ALL
 SUBSECTIONS. PLEASE PROVIDE A DETAIL.
 6) SHT P-1 KEYNOTES #11, NEW FILTERS
 SHALL BE NSF APPROVED. PLEASE SUBMIT
 MANUF. INFORMATION.
 7) SHT P-2 WATER RISER ISOMETRIC, ALL
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES, IN AN "EFFICTIVE
 RANGE", NOT IN THE CEILING AT THE TOP OF
 THE DROPS. PDI-WH 201 & MANUF. INSTALL-
 ATION INSTRUCTIONS.
 8) SHT P-5 DETAIL 8/P-5, CONDENSATE TRAP
 DETAIL. FLOOR DRAIN NOT AN APPROVED IN-
 DIRECT WASTE RECEPTOR. FLOOR SINK OR HUB
 DRAIN REQUIRED. SECTIONS 802.3 & 802.3.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692