| Plan Review Notes For Permit 03051400 |
| Permit Number |
03051400 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-06-03 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE RESUBMIT THE FOLLOWING PRIOR TO | | | ROUGH ELECTRICAL INSPECTION. | | | | | | 1} THE PLANS SHOW 2 AIR HANDLERS AND | | | ONLY ONE WAS INCLUDED IN THE ELECTRICAL | | | LOAD CALCULATION. | | | | | | 2} THE GARBAGE DISPOSAL ON THE PANEL | | | SCHEDULE SHOWS NO CIRCUIT NUMBER AND NO | | | LOAD. | | | | | | 3} THE GARAGE RECEPTACLES MUST COMPLY WI | | | TH 210-8(A)(2). | | | | | | PLEASE REVISE THE LOAD TO INDICATE | | | ACTUAL CONDITIONS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|