| Plan Review Notes For Permit 03051304 |
| Permit Number |
03051304 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-22 00:00:00 | UNSAT | | | ~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE THE LOCATION OF THE | | | DISCONNECT ON THE GARAGE PER 225-32 AND | | | SHOW GROUNDING SYSTEM PER 250-32. | | | | | | 2} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 3} PLEASE LIST THE REQ,D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE PER 210-12. | | | | | | 4} THE FEEDERS LISTED ON THE PANEL | | | SCHEDULE FOR THE GARAGE ARE #6 IN A | | | 1",AND ON THE RISER DIAGRAM SHOWN AS | | | 1/0 IN 1/2",PLEASE CORRELATE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|