Plan Review Notes
Plan Review Notes For Permit 03051304
Permit Number 03051304
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-22 00:00:00UNSAT
 ~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 DISCONNECT ON THE GARAGE PER 225-32 AND
 SHOW GROUNDING SYSTEM PER 250-32.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ,D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 4} THE FEEDERS LISTED ON THE PANEL
 SCHEDULE FOR THE GARAGE ARE #6 IN A
 1",AND ON THE RISER DIAGRAM SHOWN AS
 1/0 IN 1/2",PLEASE CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718