| Notes |
| Date |
Text |
| 2003-07-10 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | NOTE: PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | THE RISER DIAGRAM LISTS THE "NEW PANEL" | | | AS 125 A MLO,THE PANEL SCHEDULE LIST | | | SAME AS 100 AMP MAIN BREAKER,PLEASE | | | CLARIFY. | | | | | | THE PANEL SHOWS THE W.HEATER AT 20 AMPS | | | AND THE DRYER @ 20 AMPS,BUT THE LOAD | | | CALCULATIONS LIST THEM AS 4500 WATTS | | | AND 5000 WATTS RESPECTIVELY,PLEASE | | | CORRELATE | | | | | | PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG,AND SHALL HAVE NO | | | OTHER OUTLETS. | | | | | | PLEASE MAKE THE CORRECTIONS AND RESUBMIT | | | FOR REVIEW.IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|