2003-05-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS.
 A) SECTION 909.1 ONLY FIXTURES OF THE
 BATHROOM GROUP SHALL DRAIN INTO THE WET
 VENT FOR THE BATHROOM. - TIE LAUNDRY
 SINK DOWNSTREAM OF BATHROOM FIXTURES.
 B) MINIMUM SIZE PIPE FOR WASHMACHINE IS
 2". TABLE 709.1 - CLEANOUT REQUIRED MIN.
 4' ABOVE FINISHED FLOOR AT W/MACHINE.
 C) MINIMUM SIZE TRAP FOR LAUNDRY SINK IS
 1-1/2" PER TABLE 709.1.
 ---SEE RED LINE CORRECTIONS ON PLANS AND
 MAKE CORRECTONS TO PLANS AND RESUBMIT.
 D) FLA. STATUTES 61G1-16.004 MINIMUM
 INFORMATION REQUIRED, FIRM LICENSE NUM-
 BER REQUIRED ON EACH SHEET.
  