| Plan Review Notes For Permit 03051279 |
| Permit Number |
03051279 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-22 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE PROVIDE LOAD CALCULATIONS AND | | | RISER DIAGRAM OF THE EXISTING LOADS AND | | | ALL ADDED LOADS,PER 215-5 NEC.INDICATE | | | HOW SUB PANEL IS BEING FED. | | | | | | 2} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|