| Plan Review Notes For Permit 03051238 |
| Permit Number |
03051238 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-10-02 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE COMMENTS FROM | | | PREVIOUS REVIEW. | | | PLEASE SEE THAT FEEDERS ARE STILL BEING | | | SHOWN SMALLER THAN #2 AL. | | | IT WAS NOTED ON NOTE #20, HOWEVER NO | | | CHANGES HAVE BEEN MADE TO PLANS. | | | | | | 2)NOTE: IT WAS NOTED ON LAST REVIEW THE | | | PLANS WERE ONLY IN FOR PLAN REVIEW AND | | | THE CODE CHANGED ON JULY 1ST ,2003 TO | | | THE 2002 NEC. IT WAS REQUESTED TO ADJUST | | | PLANS ACCORDING TO 2002 NEC. | | | PLEASE SEE 210.12 AND SEE PLANS. | | | CIRCUITING ETC. | | | | | | 3)NOTE: PLEASE SEE THAT PLANS ARE STILL | | | ONLY IN FOR "PLAN REVIEW" AND WHEN | | | SUBMITTING FOR PERMIT, PLEASE SUBMIT | | | REQ'D # OF SETS FOR REVIEW AND STAMPING. | | | | | | 4)NOTE: PLEASE CLARIFY IF CONDUCTORS FOR | | | CLUBHOUSE SERVICE ENT AND FEEDERS ARE | | | COPPER OR ALUM? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. ONCE AGAIN, IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|