2003-10-02 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW.
 PLEASE SEE THAT FEEDERS ARE STILL BEING
 SHOWN SMALLER THAN #2 AL.
 IT WAS NOTED ON NOTE #20, HOWEVER NO
 CHANGES HAVE BEEN MADE TO PLANS.
  
 2)NOTE: IT WAS NOTED ON LAST REVIEW THE
 PLANS WERE ONLY IN FOR PLAN REVIEW AND
 THE CODE CHANGED ON JULY 1ST ,2003 TO
 THE 2002 NEC. IT WAS REQUESTED TO ADJUST
 PLANS ACCORDING TO 2002 NEC.
 PLEASE SEE 210.12 AND SEE PLANS.
 CIRCUITING ETC.
  
 3)NOTE: PLEASE SEE THAT PLANS ARE STILL
 ONLY IN FOR "PLAN REVIEW" AND WHEN
 SUBMITTING FOR PERMIT, PLEASE SUBMIT
 REQ'D # OF SETS FOR REVIEW AND STAMPING.
  
 4)NOTE: PLEASE CLARIFY IF CONDUCTORS FOR
 CLUBHOUSE SERVICE ENT AND FEEDERS ARE
 COPPER OR ALUM?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  