Plan Review Notes
Plan Review Notes For Permit 03051238
Permit Number 03051238
Review Stop B
Sequence Number 3
Notes
Date Text
2003-10-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051238
 ADD: 750 EXECUTIVE CENTER DR W
 CONT: EXECUTIVE TRUST, LTD
 TEL: (561)547-0207
 (561)547-5512
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 3RD REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE A RECORDED PLAT, PLEASE PRO-
 VIDE US IN WRITING WHICH OF THE
 PROPOSEDSTREET NAMES YOUR FIRM WILL BE
 USING.
 A) MALIBU BAY COURT
 B) MALIBU BAY DRIVE
  
 3) FAIR HOUSING, THE PLAN FROM URBAN
 DESIGN STUDIOS DOES NOT INDICATE WHERE
 THE ACCESSIBLE ROUTE FROM THE PUBLIC
 WAYIS, NOR DO WE INDICATE CURB CUTS ON
 THE PLAN. OTHER AREAS IN QUESTION ARE
 THE
 DUMPSTERS AND THE RECYCLING CENTER NEXT
 TO DUMPSTER NO WALKWAY. DETECTABLE
 WARN-INGS ON WALKING SURFACES. APPENDIX
 A4.3.11.3 STAIRWAY WIDTHS 48" WIDE EXIT
 STAIRWAY IS NEEDED TO ALLOW ASSISTED
 EVACUATION.
  
 4) SITE AMENITIES UNDERSTOOD THAT THE
 SITE AMENITIES WILL BE UNDER SEPERATE
 PERMIT AND SEPERATE REVIEW.
  
 5) THE ONLY PRODUCT TESTING REPORT SUB-
 MITTED IS THE OVERHEAD DOOR FOR THE
 CLUBHOUSE. THE LETTER FROM HOUSING
 TRUSTGROUP INDICATES THAT THE REMAINDER
 OF
 THE PRODUCT REPORTS WAS TO BE SUBMITTED
 SEPTEMBER 30. NO SUCH REPORTS WERE
 RECEIVED NOR WAS THE INFORMATION FOR
 STORM SHUTTERS OR HURRICANE
 PREPAREDNESSPLAN. SEPERATE PERMITS WITH
 ASSOCIATED
 REVEIWS AND FEES WILL BE REQUIRED!!!!!!
  
 6) 105.3.6 ADMINISTRATION CODE,
 SPECIAL INSPECTOR, RESIDENT INSPECTOR
 PROGRAM, WILL BE REQUIRED TO REGISTER
 WITH DON NEELY 805-6665.
  
 7) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITEY KNOWN, OR IS IN
 QUESTIONTHE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SUBMITTED WAS A SINGLE COPY OF A REPORT,
 SUBMIT 3 SIGNED/SEALED REPORTS.
  
 8) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
 PROVIDE WORST CASE SENERIO FOR EACH UNIT
 AND CLUBHOUSE.
  
 9) STATE STAUTE 553.895(2) MULTIFAMILY
 RESIDENTIAL BUILDINGS 3 STORIES OR
 GREATER REQUIRE FIRE SPRINKLER PLANS
 TO BE SUBMITTED AS PART OF THE PERMIT
 READY PACKAGE. SEPERATE PLANS WILL ALSO
 BE REQUIRED FOR THE FIRE SPRINKLER
 PERMIT!!!!
  
 10)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 *************CLUBHOUSE****************
  
 11)2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM C-1063.HI RIB LATH TO BE NAILED @
 4" O.C. W/ 2" ROOFING NAILS OR STAPLES.
 SHEET AM-4.
  
 12)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 USP HTD19- 2560 UPLIFT.
  
 NOTE TRUSSES ARE TO BE DESIGNED WITH
 10 LBS. LIVE LOAD!!!!!
  
 13) BREEZEWAYS: PLANS INDICATE A 2 HR.
 WALL BUT ONLY A 1HR "C" LABEL DOOR.
 705.1.3.4 REQUIRES A 1 1/2HR "B" LABEL
 DOOR, AVERAGE TEMPERATURE RISE DEVELOPED
 ON THE UNEXPOSED SIDE SHALL NOT EXCEED
 450 DEGREES AT THE END OF 30 MIN OF
 STANDARD FIRE TEST EXPOSURE.
  
 14) PLANS EITHER NOT SEALED OR MISSING
 PAGES:
 SET# 1 REVIEW SET
 COMPLETE BUT UNSEALED SHEETS
 SET# 2 ED-1 IS OLD
 SET# 3 ED-1 IS OLD
 MISSING COVER
 MISSING S-T2.1
 S-T2.2
 SA.1
 SA.2
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved