Plan Review Notes For Permit 03051238
Permit Number 03051238
Review Stop P
Sequence Number 1
Notes
Date Text
2003-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SHT AU-4 DETAIL 3/ADT-4, BACKING FOR
 TUB & W/C TO COMPLY WITH FHA DESIGN MAN-
 UAL. SEE PAGE 6.9 - HEIGHT, LENGTH &
 WIDTH TO BE THE SAME AS SHOWN.
 2) SHTS PT1.3, PT1A.3, PT2.3, & PT2A.3,
 FULL OPEN VALVES REQUIRED AT THE BASE OF
 EVERY WATER RISER. SECTION 606.1(3)
 3) SHT PD-1 PLUMBING GENERAL NOTES:
 #2 PVC NOT APPROVED FOR DISTRIBUTION
 PIPE. SEE TABLE 605.5
 #6 DIELECTRIC UNIONS APPROVED FOR GAS
 PIPING ONLY. PLEASE DELETE REFERENCE.
 4) SHT PD-1 WATER HEATER DETAIL - NOTE
 CONCERNING AIR CHAMBERS. AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE REFEREN-
 CE. - THERMAL EXPANSION CONTROL REQUIRED
 PLEASE SHOW ON DETAIL. SECTION 607.3.2
 5) SHT PM-2 INSTANTANEOUT WATER HEATERS,
 MANUF. INFO. REQUIRED. W/HEATERS SHALL
 BE LISTED WITH AN APPROVED TESTING
 AGENCY.
  