Plan Review Notes
Plan Review Notes For Permit 03051238
Permit Number 03051238
Review Stop M
Sequence Number 1
Notes
Date Text
2003-05-28 00:00:00DENIED:CLUBHOUSE
 1.INDICATE WHAT TYPE OF "MAITENANCE"
 WILL BE DONE IN THE MAINTENANCE GARAGE.
 PLEASE PROVIDE CLARIFY IF ANY FLAMABLES
 OR COMBUSTIBLES ARE TO BE STORED IN THIS
 AREA.SHOW COMPLIANCE WITH 2001 FBC(M)
 TABLE 403.3 FOR VENTILATION REQUIREMENTS
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS OR TO A
 SUPERVISORY SIGNAL TO BE INDICATED AT A
 CONSTANTLY ATTENDED LOCATION.
  
 APARTMENTS:
 1.PLEASE NOTE AS PER THE FAIR HOUSING
 ACT, ENVIRONMENTAL CONTROLS SHALL BE AT
 AN ACCESSIBLE LOCATION.
  
 2.PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) NATURAL MEANS 402.2 OR
 MECHANICAL MEANS TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.